Characteristic impedance, propagation constant, exact ABCD constants and the sending-end quantities, regulation and efficiency of a long three-phase line with uniformly distributed R, X and shunt B (the Ferranti rise appears as a negative regulation at light load).
A = \cosh\gamma l,\ B = Z_c\sinh\gamma l,\ C = \frac{\sinh\gamma l}{Z_c},\quad Z_c = \sqrt{\frac{z}{y}},\ \gamma = \sqrt{zy}
Inputs
Vr receiving-end line-to-line voltage [V]P load real power (three-phase) [W]pf load power factorR line resistance per phase (total) [ohm]X line reactance per phase (total) [ohm]B total shunt susceptance of the line per phase [S]pf_type lagging (default) or leading load choice optional
Returns
Vs sending-end line voltage [V]delta_deg angle of the sending voltage ahead of the receiving voltage, degreesIs sending-end current [A]Ps sending-end real power [W]losses line losses (three-phase) [W]regulation_pct voltage regulation (V_s/|A| - V_r)/V_r in percentefficiency_pct transmission efficiency in percentA_mag |A| (= |D|)A_angle_deg angle of A in degreesB_mag |B| in ohms [ohm]B_angle_deg angle of B in degreesZc_mag characteristic (surge) impedance magnitude [ohm]Zc_angle_deg angle of Zc in degreesalpha_l attenuation alpha l in nepersbeta_l phase shift beta l in radians
Applies when
- uniformly distributed parameters
- balanced load
Example
m.ask("Long line: Vr = 400 kV, P = 1 MW, pf = 1, R = 0 ohm, X = 100 ohm, B = 400 uS")
→ Vs = 392027 V, delta_deg = 0.0362951, Is = 91.7723 A, Ps = 1e+06 W, losses = 0 W, regulation_pct = 2.00641e-05, efficiency_pct = 100, A_mag = 0.980067, A_angle_deg = 0, B_mag = 99.3347 ohm, B_angle_deg = 90, Zc_mag = 500 ohm, Zc_angle_deg = 0, alpha_l = 0, beta_l = 0.2